Springhouse Estates Water District

◄ Back
May 3, 2021 8:26 AM

Springhouse Estate Water Service Interruption - NYSEG lost 3Phase service to the plant. 5/3/21

NYSEG lost 3Phase service to the plant. The Generator didn't transfer on as a result of a mouse getting into the generator. The mouse chewed through battery charge wire. (the generator runs weekly for test and was fine last week.) Repairs were made.

NYSEG lost 3Phase service to the plant. The Generator didn't transfer on as a result of a mouse getting into the generator. The mouse chewed through battery charge wire. (the generator runs weekly for test and was fine last week.) Water Service was lost around 6:30am. Operators were on location around 6:55. Generator Company called and arrived around 7:50. Repairs were made. NYSEG Service was restored at 8:05 and Generator was back in service at 8:10. Water Service was restored around 8:08